ProControl Series 2plus
Type A
Product Specification
The next generation Type A ProControl features a capacity of
up to 78 industrially-hardened inputs and outputs in a small and easy-to-use
package. The Series 2plus contains everything you need
for the core of your control/telemetry system, including the ability to drive motor starters, solenoids and other
devices directly from built-in relay outputs. The Series 2plus
includes expanded datalogging and reporting capability, a built-in power supply
for your instruments and transducers, as well as pluggable connectors for all
I/O. The Type A features higher I/O counts, large datalog memory, greater
process control capability, and a vacuum
fluorescent display.
| |
Model A1
$3,495 |
Model A2
$3,995 |
|
Inputs |
|
|
|
Discrete |
Sixteen (16) protected discrete inputs. Support for 4 flowmeters or
pulse accumulators with rates to 500Hz. |
Twenty-Four (24) protected discrete inputs (Eight of these are status
inputs). Support for 4 flowmeters or pulse accumulators with rates to
500Hz. |
|
Analog |
Sixteen (16) 4-20ma inputs with built-in 24Vdc supply. Inputs are surge
and short-circuit protected and may also be used as discrete inputs |
Sixteen (16) 4-20ma inputs with built-in 24Vdc supply. Inputs are surge
and short-circuit protected and may also be used as discrete inputs |
|
Outputs |
|
|
|
Discrete |
Twenty-Two (22) relay outputs rated at 1/2A, 120VAC |
Thirty (30) relay outputs rated at 1/2A, 120VAC |
|
Analog |
|
Eight (8) 4-20ma outputs. PID loop control. |
|
Datalogging |
|
|
|
Discrete |
30,000 points standard. All logging occurs on change of state. |
30,000 points standard. All logging occurs on change of state. |
|
Analog |
80,000 points standard (5000 per channel). Flow totals (50 per channel) |
80,000 points standard (5000 per channel). Flow totals (50 per channel) |
|
Event |
10,000 points standard. |
10,000 points standard. |
|
Communications |
|
|
|
Modem |
ProView Software, PC to ProControl Interface - 9600 baud. |
|
FAX |
Alarm and Status Reports. Group 3,
Class 2 FAX reporting at 9600 baud |
|
Pager |
TAP standard numeric and alpha-numeric paging at 300 to 2400 baud. |
|
Local |
Direct RS-232 Serial interface with automatic local/remote switching. |
|
e-mail |
Via third-party service, alarm and status reports. |
|
Network |
Optional - Can be linked via RS-485 for distributed
control or higher I/O counts |
|
User Interface |
|
|
|
Display |
VFD (Vacuum Fluorescent Display) 2 x 20 character display |
|
Keypad |
2 x 6 membrane keypad. |
|
LEDs |
LEDs: System Status, Communications Link, Networking |
|
Process Control |
|
|
|
System |
Up to 64 regular system processes total with 16 startup and 16 shutdown
processes. Processes run every 0.35 seconds. |
|
Alarms |
Generate shutdowns, two FAX reports and/or two Pager messages. |
|
Loops |
PID loop control with user control of setpoint, proportional, integral
and differential gains and max change per calculation. Also open loop
proportional algorithm. (A2) |
|
Power |
|
|
|
System |
10VAC, 30VA, external transformer provided |
|
I/O Supply |
24 VDC, 15V and 9V available for powering sensors/instruments. |
|
Environmental |
|
|
|
Dimensions |
13.5" long x 6" wide x 3.5" high. |
|
Weight |
7 lbs. |
|
Power Dissipation |
25W |
|
Operating Temperature |
-20C to +50C |
|
Humidity |
95% R.H. non-condensing |
|