Home Up Contents

Type B Specification

 Download ProView 2.16

 

Products
Documents
ProView

ProControl Series 2plus

Type B

Product Specification

The next generation Type B ProControl features a capacity of up to 51 industrially-hardened inputs and outputs in a small and easy-to-use package.  The Series 2plus contains everything you need for the core of your control/telemetry system, including the ability to connect directly to 120V inputs, and to drive motor starters, solenoids and other devices directly from built-in relay outputs.  The Type B includes expanded datalogging and reporting capability, a built-in power supply for your instruments and transducers, as well as pluggable connectors for all I/O.  It's a truly capable SCADA system for your operation.

 

Model B1

$2,495

Model B2

$2,995

Inputs

   

Discrete

Twelve (12) protected discrete inputs. Support for 4 flowmeters or pulse accumulators with rates to 200Hz.

Sixteen (16) protected discrete inputs. Eight (8) optically isolated inputs.  Support for 6 flowmeters or pulse accumulators with rates to 200Hz.

Analog

Eight (8) 4-20ma inputs with built-in 24Vdc supply. Inputs are surge and short-circuit protected and may also be used as discrete inputs.

Ten (10) 4-20ma inputs with built-in 24Vdc supply. Inputs are surge and short-circuit protected and may also be used as discrete inputs.

Outputs

   

Discrete

Fourteen (14) relay outputs rated at 1/2A, 120VAC

Fourteen (14) relay outputs rated at 1/2A, 120VAC

Analog

 

Five (5) 4-20ma outputs. PID loop control.

Datalogging

   

Discrete

2,000 points standard. 30,000 points optional. All logging occurs on change of state.

2,000 points standard. 30,000 points optional. All logging occurs on change of state.

Analog

16,000 points standard (2000 per channel). 80,000 points optional. Flow totals (50 per channel)

20,000 points standard (2000 per channel). 100,000 points optional. Flow totals (50 per channel)

Event

2,000 points standard. 10,000 points optional.

2,000 points standard. 10,000 points optional.

Communications

 

Modem

ProView Software, PC to ProControl Interface - 9600 baud.

FAX

Alarm and Status Reports. Group 3, Class 2 FAX reporting at 9600 baud

Pager

TAP standard numeric and alpha-numeric paging at 300 to 2400 baud.

Local

Direct RS-232 Serial interface with automatic local/remote switching.

e-mail

Via third-party service, alarm and status reports

Network

Optional - Types B1 and B2 can be linked via RS-485 for distributed control or higher I/O counts

User Interface

 

LCD

2 x 20 character display 

Keypad

2 x 6 membrane keypad 

LEDs

LEDs: System Status, Communications Link, Networking

Process Control

 

System

Up to 32 regular system processes total with 8 startup and 8 shutdown processes. Processes run every 0.35 seconds.

Alarms

Generate shutdowns, two FAX reports and/or two Pager messages.

Loops

PID loop control with user control of setpoint, proportional, integral and derivative gains and max change per calculation. Also open loop proportional algorithm.

Power

 

System

10VAC, 30VA, external transformer provided

I/O Supply

24 VDC, 15V and 9V available for powering sensors/instruments.

Environmental

 

Dimensions

13.5" long x 6" wide x 3.5" high.

Weight

6 lbs.

Power Dissipation

25W

Operating Temp.

-20C to +50C

Humidity

95% R.H. non-condensing